CI75-495x400.jpg

PRINCIPLES OF OPERATION

16kV 500 Joule Surge Generator

The SG50016 surge generator generates voltages ranging from 2.5 to 16kV and is typically used in the location of faults in medium voltage networks. The maximum storage energy of the capacitor is 500 J at 4,10 and 16kV. All surge generators generate high voltages from the mains
supply voltage, which is rectified and used to charge capacitors, which are in turn discharged into a faulty cable at adjustable intervals.

The unit has an internal automatic dump contactor which discharges both the unit and the cable under test. This is activated when the unit is turned off or when a power failure occurs.

It can be operated in the single shot or continuous pulsing method if correct selection is made.

The unit can also be used to perform insulation resistance tests up to the selected output levels.

Adret SG50016
SURGE GENERATOR

16kV 500 Joule Surge Generator

SPECIFICATION

Supply Voltage : 220-240VAC
Supply Current : 10A
Output Voltage : 2.5-16kV
Surge Energy : 500 at 4, 8 and 16kV
Weight : 45kg
Dimensions : 540x315x330mm excluding lid
Impulse Rate : 6 or 10 PPM
Enclosure : Aluminium, Electrostatically powder coated
Voltage Level Adjustment : Switched between 2.5, 4, 5, 8, 10, 16kV
Meters : Voltage Indication and Leakage current
Proof Testing : Yes with Leakage current indication
PCA Interface : Built In

Output Power : 5W Continuous/Pulsed
Power Supply : 6 X 1.5V C Cells (Alkaline)
Weight : 1Kg
Battery Indication : Red/Green LED
Battery Life : Approximately 40Hrs
Operating Freq : 625Hz
Range : 20km
Signal : Pulsed/continuous sine wave
Output Protection : Matching transformer isolated
Operating Temp : 0C to +50C

ACCESSORIES

Lid : Aluminium with canvas bag for test cables
Test Cables : 5m HT lead with high current clamps
Earth Lead : 5m yellow/green
Mains Lead : 2m 3 core